The water chiller contains demineralised water, mixed with a little coolant.

Quality definitions of demineralised water

Section titled “Quality definitions of demineralised water”

Demineralised water (demiwater) is deionised water for technical applications that need pure water. It is not suitable for drinking.

Parameter (symbol) Unit Minimum Maximum Average
Conductivity at 20 °C (EC) µS/cm <0.2 <0.06
Degassed conductivity at 20 °C (EC) µS/cm <0.2 <0.06
Silicate (SiO2) mg/l <0.03 <0.06
Total dissolved solids (TDS) mg/l N.A. N.A.
Iron (Fe) mg/l <0.1 <0.005
Copper (Cu) mg/l <0.05 <0.005
Ammonia (NH3) mg/l <2 <0.010
Total organic carbon (TOC) mg/l N.A. 0.002 - 0.010
Turbidity NTU N.A. N.A.
Sodium (Na+) mg/l N.A. <0.020
Sulphate (SO4) mg/l N.A. N.A.
Chloride (Cl-) mg/l N.A. <0.010
Free / total chlorine (Cl2) mg/l N.A. N.A.
Temperature °C 3 40 12
Calcium (Ca) mg/l N.A. <0.010
Magnesium (Mg) mg/l N.A. <0.005
Acidity / alkalinity at 25 °C pH 5.5 7.5 7
Hardness mmol/l <0.04 0
Bacteria CFU/ml <50 0

The physical and chemical quality stated above applies at the supplier’s truck loading station only.

1 ppm (part per million) = 1 mg/l. µS/cm = microsiemens per centimetre. The supplier’s buffer tanks for demineralised water are open to the atmosphere, so CO2 dissolves in the water and raises its conductivity. That is why conductivity is given both with and without the dissolved CO2 (degassed).

The water is produced by filtration, softening, reverse osmosis (RO) and mixed-bed ion exchange. It is not chlorinated, and any free chlorine in the raw feed water does not pass through the installation, so free and total chlorine are given as not applicable.